OPC UA Client Failover Control
N
Nile Ellis
Add functionality to allow for a OPC UA client connection to be switched from the failover back to the primary connection and visa versa. Adding a system tag to control this as well as a tag to provide the status feedback would be very useful and would help add polish to the failover feature.
Log In
T
Théo BASTY
Adding on this, I think it would be a great feature to have better handling of the OPC failover in edge cases.
Mainly one I've seen and I'm experiencing, working with Schneider M580 Redundant PLCs for which you need to work with the BMENUA0100 OPCUA server of the primary CPU but they don't cut the connection on the backup CPU.
At least having a way to know which endpoint is used by the gateway, and the possibility to trigger the failover by script would be sufficient to handle such cases